Enter any two values, then press Calculate. The other two are worked out for you.

V
A
Ω
W

Don’t know the power yet? Calculate heater wattage →

Worked examples

Single-phase. A heater is rated 2,300 W on a 230 V supply. What current does it draw, and what is its resistance?

  1. Inputs: V = 230 V, P = 2,300 W.
  2. Current: I = P ÷ V = 2,300 ÷ 230 = 10 A.
  3. Resistance: R = V² ÷ P = 52,900 ÷ 2,300 = 23 Ω.

Three-phase. A balanced 9 kW heater bank runs on a 415 V three-phase supply.

  1. Line current, star or delta: IL = P ÷ (√3 × VL) = 9,000 ÷ (1.732 × 415) = 12.52 A.
  2. Star: branch voltage = 415 ÷ 1.732 = 239.6 V, and R per branch = 415² ÷ 9,000 = 19.14 Ω.
  3. Delta: branch voltage = 415 V, and R per branch = 3 × 415² ÷ 9,000 = 57.41 Ω.

Equations used

Single-phase and DC, for a resistive load:

V = I × R     P = V × I = I² × R = V² ÷ R

Balanced three-phase resistive load, where VL is line voltage and IL is line current:

P = √3 × VL × IL

Star (Y): branch voltage = VL ÷ √3, branch current = IL

Rbranch = VL² ÷ P

Delta (Δ): branch voltage = VL, branch current = IL ÷ √3

Rbranch = 3 × VL² ÷ P

Assumptions and limits

  • The load is purely resistive, as heating elements are. Power factor is taken as 1.
  • The three-phase mode assumes three equal branches and a balanced supply.
  • Resistance is the value at operating temperature. Many element alloys have a lower resistance when cold, so inrush current can be higher than the figure shown.
  • Supply voltage tolerance changes power with the square of voltage: 10% more voltage gives about 21% more power.
  • Results are for estimating. Size cables, contactors and protection to the applicable electrical code.