Ohm’s law calculator
Work out voltage, current, resistance and power for a resistive load, or the currents and branch resistance of a balanced three-phase heater bank.
Enter any two values, then press Calculate. The other two are worked out for you.
For a balanced three-phase resistive heater bank: three equal elements (branches), connected in star or delta. Enter the line voltage and one value you know.
Measured between any two supply lines, for example 415 V.
Results
- Total power (all three branches)
- Line voltage (between any two supply lines)
- Branch voltage (across each element)
- Line current (in each supply line)
- Branch current (through each element)
- Resistance per branch
- Power per branch
Don’t know the power yet? Calculate heater wattage →
Worked examples
Single-phase. A heater is rated 2,300 W on a 230 V supply. What current does it draw, and what is its resistance?
- Inputs: V = 230 V, P = 2,300 W.
- Current: I = P ÷ V = 2,300 ÷ 230 = 10 A.
- Resistance: R = V² ÷ P = 52,900 ÷ 2,300 = 23 Ω.
Three-phase. A balanced 9 kW heater bank runs on a 415 V three-phase supply.
- Line current, star or delta: IL = P ÷ (√3 × VL) = 9,000 ÷ (1.732 × 415) = 12.52 A.
- Star: branch voltage = 415 ÷ 1.732 = 239.6 V, and R per branch = 415² ÷ 9,000 = 19.14 Ω.
- Delta: branch voltage = 415 V, and R per branch = 3 × 415² ÷ 9,000 = 57.41 Ω.
Equations used
Single-phase and DC, for a resistive load:
Balanced three-phase resistive load, where VL is line voltage and IL is line current:
Star (Y): branch voltage = VL ÷ √3, branch current = IL
Delta (Δ): branch voltage = VL, branch current = IL ÷ √3
Assumptions and limits
- The load is purely resistive, as heating elements are. Power factor is taken as 1.
- The three-phase mode assumes three equal branches and a balanced supply.
- Resistance is the value at operating temperature. Many element alloys have a lower resistance when cold, so inrush current can be higher than the figure shown.
- Supply voltage tolerance changes power with the square of voltage: 10% more voltage gives about 21% more power.
- Results are for estimating. Size cables, contactors and protection to the applicable electrical code.
Need a heater or a heater bank built to these figures? Send the voltage, power and application and we will quote it.